Chiller GPM Calculator

Water Side

GPM CALCULATOR

Estimate chiller water flow from design pressure drop and current pressure readings.

Evaporator Flow

Evaporator

GPM
Tap to switch
PSI
PSI

Calculated flow

Chiller Trend

Condenser Flow

Condenser

GPM
Tap to switch
PSI
PSI

Calculated flow

Chiller Trend

Flow is an estimate, not a direct flow measurement.

Want to understand the method? Read the Chiller GPM Pressure Drop guide →
Advanced

METHOD
Pressure Drop Method

FORMULA
GPM₂ = GPM₁ × √(ΔP₂ / ΔP₁)

EXPLANATION
This formula estimates water flow from the current pressure drop and the chiller’s design flow and design pressure drop.

Assumptions and limitations: Design flow and design pressure drop are required. Measured pressure difference is entering pressure minus leaving pressure. Unit conversion occurs before the pressure-drop ratio is calculated. This is an estimate, not a direct flow measurement. Results depend on correct design data and valid pressure readings.