Condenser Tons Calculator
Condenser Tons Calculator
Estimate condenser heat rejection from water flow and condenser-water temperature rise.
Condenser Water Readings
Enter measured flow and entering and leaving water temperatures from the same operating condition.
GPM
°F
°F
Estimated Condenser Load
— tons

Condenser-water ΔT—
Method and assumptions
Formula
Condenser tons = GPM × (leaving water temperature − entering water temperature) ÷ 24.
Assumption
The factor of 24 assumes water. Glycol or another heat-transfer fluid requires correction for the actual fluid properties and concentration.
Limit
This estimates condenser-side heat rejection; it does not, by itself, establish equipment condition or root cause.