HVAC Electrical Calculators | Chiller Trend

Electrical Calculators

Electrical calculators for quick field checks.

Electrical
Ohm’s Law & Power

Enter two values to calculate the other two.

Known Values

Optional
V
Optional
A
Optional
Ω
Optional
W
Calculated Values
Ohm’s Law result
Second calculated value
Chiller Trend
Advanced

Formula: V = I × R. P = V × I. Related forms are used depending on which two values are entered.

Assumptions: Ideal DC and simple resistive-circuit relationships.

Warnings: Measure resistance only on a de-energized circuit. Motors, coils, transformers, and drives require additional electrical relationships.

Electrical
Three-Phase kW

Estimate real power from voltage, current, and power factor.

Electrical Readings

Enter line voltage and line current. Replace the default power factor if measured.

Required
V
Required
A
Default
PF
Estimated real power
Chiller Trend
Apparent power
Power factor used
Advanced

Formula: kW = volts × amps × 1.732 × power factor ÷ 1000.

Assumptions: Voltage and current are treated as balanced three-phase line values.

Warnings: If power factor is estimated instead of measured, calculated kW is also estimated.

Electrical
Current Imbalance

Calculate current imbalance from three phase-current readings.

Phase Current

Enter L1, L2, and L3 current.

Required
A
Required
A
Required
A
Current imbalance
Chiller Trend
Average current
Maximum deviation
Advanced

Formula: % imbalance = maximum deviation from average ÷ average current × 100.

Assumptions: All three readings are taken under the same operating condition and are directly comparable.

Warnings: Verify readings with a calibrated meter and compare against equipment-manufacturer limits.

Electrical
VFD Frequency to Motor RPM

Calculate synchronous motor speed and nameplate slip.

Motor and VFD

Enter VFD frequency and motor poles. Add nameplate full-load RPM to calculate nameplate slip.

Required
Hz
Default
Hz
Optional
RPM
Reset
Synchronous motor speed
Chiller Trend
Base synchronous RPM
Nameplate slip RPM
Nameplate slip
Advanced

Formula: Synchronous RPM = 120 × frequency ÷ poles. Base synchronous RPM = 120 × base frequency ÷ poles. Slip RPM = base synchronous RPM − nameplate full-load RPM. Slip % = slip RPM ÷ base synchronous RPM × 100.

Assumptions: Nameplate slip describes the rated full-load condition at the motor base frequency.

Warnings: Actual shaft RPM under load depends on operating load, motor characteristics, and VFD control behavior. This calculator does not predict actual loaded shaft RPM at arbitrary VFD frequencies.

Electrical
Transformer VA / Control Amps

Calculate required VA or available control current.

Transformer Inputs

Choose what to calculate, then enter the requested values.

Required
V
Required
A
Required transformer capacity
Chiller Trend
Secondary voltage
Load current
Advanced

Formula: VA = volts × amps. Amps = VA ÷ volts.

Assumptions: This uses the basic single-phase volt-ampere relationship for transformer secondary loads.

Warnings: The result does not add sizing margin or account for inrush, duty cycle, simultaneous loads, fuse sizing, conductor sizing, or manufacturer requirements.