Pressure Testing Calculators
Field calculators
Pressure Testing
Tools for nitrogen correction, vacuum decay, and evacuation work.
Nitrogen Pressure Temperature Correction
Estimate expected nitrogen pressure after the test temperature changes.
Expected pressure now

Advanced settings
YORK Nitrogen Pressure Hold Time
Determine the required nitrogen pressure-test hold time from YORK vessel diameter and length.
Supported source range: 2.0–24.0 ft. Length is rounded to the nearest 0.1 ft per YORK.
Required hold time
If there is no pressure loss, proceed to evacuation. If pressure drops, proceed to leak testing.
Procedure notes
Before this hold test, YORK directs an initial evacuation to 5 mmHgA, nitrogen vapor charging only, and pressure buildup to the DWP on the vessel data plates.
YORK Trace Gas Leak Test Setup
Look up YORK trace-gas type, detector sensitivity, and test pressures by refrigerant.
Trace gas leak test setup
Procedure notes
Use a high-resolution analog gauge with 2 psi increments and a 3 in. (76.2 mm) or larger dial. Start at 5 mmHgA—do not go below it. Charge vapor only to the selected initial pressure, add dry nitrogen to the final pressure, verify trace gas at the vapor service valve, then test joints and factory welds with a suitable detector. YORK also provides tube/waterbox follow-up steps.
Vacuum Decay Test
Check micron rise against an OEM/model-specific standing vacuum limit.
Standing vacuum readings
Match the procedure to the equipment model and job requirement.
Observed rise