Chiller & HVAC Field Calculators
💧 PSI ↔ Feet of Water
🌡️ Temperature Conversion
🌡️ Delta T Calculator
🏢 Water Hydrostatic Pressure
💧 Pump Head Calculator
🧰 Pressure Drop / Head Loss
⚙️ PSIG ↔ PSIA
🧭 Vacuum Pressure Conversions
📈 Compression Ratio
🌡️ Wet-Bulb Estimate
Field Notes
PSI / feet of water: This is commonly used for pump head, pressure drop, flow checks, and hydronic troubleshooting.
Temperature conversion: Use this when readings, manuals, or setpoints are given in a different temperature scale.
Delta T: This value is often used for chilled-water load, condenser-water load, coil checks, tower range, and heat-transfer review.
Hydrostatic pressure: Use vertical height from the pressure point to the top of the water column. This is static pressure only and does not include pump pressure, flow loss, or pressure drop through piping.
Pump head: Use suction and discharge pressures taken at comparable elevations when possible. Elevation difference affects the pressure reading.
Pressure drop: Use this for strainers, coils, heat exchangers, chiller barrels, and other components. Higher pressure drop can indicate restriction, fouling, closed valves, incorrect flow, or a measurement issue.
PSIA / PSIG: These tools use 14.7 psia as standard atmospheric pressure. Actual atmospheric pressure changes with elevation and weather.
Vacuum: Inches Hg vacuum is based on pressure below standard atmospheric pressure. Use PSIG-to-inches-Hg-vacuum only for readings below 0 PSIG. Positive PSIG is pressure above atmosphere, not vacuum.
Wet-bulb: The wet-bulb tool is an estimate from dry-bulb temperature and relative humidity. For tower control, commissioning, or performance verification, use a measured wet-bulb reading when accuracy matters.
Need more than quick field math? Chiller Trend turns readings into structured logs, calculated outputs, trends, and defensible findings.