The Next Layer
Chiller Performance Snapshot
Turn one set of inspection readings into a calculated performance snapshot with flow, load, efficiency, and cooling tower context for the field record.
Operating Conditions
Enter measured ambient conditions. Wet bulb is used for tower approach.
Evaporator Water Side
Design pressure drop defaults to feet of water. Measured entering and leaving pressures default to PSI. Tap any unit to switch it.
Condenser Water Side
Design pressure drop defaults to feet of water. Measured entering and leaving pressures default to PSI. Tap any unit to switch it.
Electrical Input
Total chiller kW is used with calculated evaporator tons to determine kW/ton.
Chiller Performance Snapshot
Calculated Results
Advanced: formulas, assumptions, and warnings
Flow estimate
Estimated GPM = Design GPM × √(Measured ΔP ÷ Design ΔP)
Every pressure field can be entered independently in feet of water or PSI. PSI values are converted using 2.31 ft H₂O per PSI before the pressure-drop ratio is calculated.
Evaporator load
Tons = GPM × Evaporator ΔT × 500 ÷ 12,000
Condenser heat rejection
Condenser tons = GPM × Condenser ΔT × 500 ÷ 12,000
Efficiency
kW/ton = Total chiller kW ÷ Calculated evaporator tons
Warnings
Use stable readings and verified instruments when accuracy matters. Pressure-drop flow is an estimate and depends on correct design data, pressure taps, fluid properties, and measurement quality.
Need the history behind the numbers?
Chiller Trend saves the readings, calculations, and operating context so service teams can compare inspections and see what changed.
See How Chiller Trend Works →